2010 Scottish Building Regulations Section 6 Update
Non-Domestic Guidance

The Building Standards Division of the Scottish Government has released the details of the forthcoming changes to Section 6 of the Scottish Building Regulations.  The changes will come into force on the 1st of October 2010.  The main changes are summarised in this article.

All new buildings will be required to show (through SBEM calculation methodology) a 30% reduction in CO2 emissions from the 2007 standards.  The SBEM methodology will be revised to include this improvement factor so designers will still simply be demonstrating compliance with the Target Emissions Ration (TER).

The maximum acceptable U-values have been revised for new buildings, extensions and conversions of existing buildings.  The area weighted maximum acceptable values are shown in table 1.

Type of Element

2010 Area Weighted Average U-value for all elements of the same type (W/m²K)

 

New Buildings

Shell and Fit Out Buildings

Extensions to Existing Buildings

Conversions of Existing Buildings

Wall

0.27

0.23

0.25

0.30

Floor

0.22

0.20

0.20

0.25

Roof

0.20

0.15

0.15

0.25

Windows, doors and roof lights

2.0

1.60

1.60

1.60

Table 1: Maximum allowable U-values

Shell buildings should be designed to achieve a maximum air permeability of 7m³/m².h @ 50Pa.  Testing will be required on completion of the shell and again on completion of the fit out works.  All other buildings should be designed to achieve an air permeability of 10m³/m².h @ 50Pa or less although this is a recommendation only.  Air tightness testing will be required from 1st May 2011.

Seasonal efficiency requirements for heating systems have been changed and a minimum efficiency has been added for biomass boilers.  Table 2 shows the proposed efficiencies required.

Fuel Type

Boiler System

Minimum Boiler Seasonal Efficiency (based on gross calorific value)

Gas (natural)

Single

Multiple

86%

82% for any individual boiler and

86% for the overall multi-boiler system

Gas (LPG)

Single

Multiple

87%

82%

87% for the overall multi-boiler system

Oil

Single

Multiple

84%

82%

84% for the overall multi-boiler system

Biomass

 

75% for independent automatic pellet/woodchip boilers;

65% for independent gravity-fed boilers <20.5kW

Table 2: Boiler seasonal efficiencies

The only revision to the minimum allowable efficiencies of heat pumps is the distinction of those providing heat for domestic hot water and those providing heat for space heating only.  The minimum heating COP for heat pumps for space heating only has increased from 2.0 to 2.2.  The minimum COP required for heat pumps providing domestic hot water remains at 2.0.

There are changes to the minimum thermal efficiencies allowed for gas and oil firing warm air systems and radiant heaters as shown in tables 3 and 4.

System

Minimum Thermal Efficiency (based on net calorific value)

Gas firing forced convection heater without a fan complying with EN 621

91%

Fan assisted gas-firing forced convection complying with EN 1020

91%

Direct gas firing forced convection heater complying with EN 525

100%

Oil firing forced convection complying with EN 13842

91%

Table 3: Gas and oil firing warm air systems minimum thermal efficiency

System Type

Minimum Thermal Efficiency (based on net calorific value)

Thermal

Radiant

Luminous (flueless)

86%

55%

Non-luminous (flueless)

86%

55%

Non-luminous (flued)

86%

55%

Multi-burner radiant heaters

91%

N/A

Table 4: Radiant heaters minimum efficiency

There are no changes to the minimum allowable thermal efficiencies for domestic hot water systems. 

CHP QA Quality Index guidance has been clarified to cover systems less than 500kWe but greater than 5kWe.  Micro CHP systems less than 5kWe are dealt with in the Domestic Technical Guidance.  The minimum combined heat and power quality index for all types of CHP should be 105 with a power efficiency greater than 20%.  The CHP unit should operate as the lead heat generator and be sized to supply no less than 45% of the annual heating demand.  CHP may be used as the main or supplementary heat source in community heating or district heating schemes.

Further information has been included in the regulations in respect of circulators and water pumps when used in closed systems.  Circulators up to 2.5kW should have a minimum rating of Band C in respect of energy efficiency, in accordance with the Europump Labelling Scheme.  Variable speed glandless circulators should be used on variable volume systems.  Any water pump rated at more than 750W should be fitted with, or controlled by, an appropriate variable volume system.  On water pump booster sets with an open loop circuit the static head should be checked before an appropriate variable speed controller is used.

The controls package for air to water heat pumps must include defrost control of the external airside heat exchanger. 

Minimum controls packages have been introduced for gas and oil firing warm air systems and radiant heaters.  When radiant heaters are installed in new or existing buildings the controls package should include as a minimum; time control and space temperature control with black bulb sensors. 

When installing gas and oil firing warm air systems in new and existing buildings the controls package must feature, as a minimum; time control, space temperature control and, for buildings with a floor area greater than 150sqm, zone control. 

All other system control package minimum guidelines remain the same as in 2007 standards.

Minimum lighting efficiencies have been included for artificial lighting with the exception of emergency lighting or specialist process lighting such as theatre spotlights and lighting in hospital operating theatres.  The minimum standards for efficacy are shown in table 5.

Lighting Type

Average Initial Efficacy

General lighting in office, industrial and storage areas

Not less than 55 luminaire lumens per circuit-watt (1)

General lighting in other types of space

Not less than 55 lamp lumens per circuit-watt

Table 5: Minimum lighting efficacy in buildings

(1)   Efficacy of not less than 55 luminaire lumens per circuit-watt for installations in existing buildings.  When calculating the average luminaire lumens per circuit-watt, the circuit watts for each luminaire may first be multiplied by the control factors in table 6.

Lighting Output Control

Control Factor

a.    Luminaire in daylit space, light output controlled by photoelectric switching or dimming control, with or without override.

0.90

b.    Luminaire in a space likely to be unoccupied most of the time and where a sensor switches off the lighting in the absence of occupants but switching on is done manually except where this would be unsafe

0.90

Circumstances a. and b. combined

0.85

None of the above

1.00

Table 6: Luminaire control factors for use in existing buildings

More detailed control requirements have been introduced for general and display lighting.  These are shown in table 7.

Space Classification

Control Type

Owned

(small room for one of two people who control the lighting)

Manual, by door

 

Shared

(multi-occupied area, e.g. an open plan office or factory production area)

Flexible manual switching, e.g. pull cords or wireless transmitter.

 

Temporarily owned

(where people are expected to operate the lighting control while they are there, e.g. a hotel room or meeting room.)

All types and ratings

 

Occasionally visited

(used for short periods of time, e.g. store room or toilet)

Presence or absence detection (avoided use where this may cause a hazard or inconvenience, e.g. in an accessible toilet), manual control

Unowned

(where individual users require lighting but are not expected to operate controls, e.g. a corridor or atrium)

1.             Time switching

2.             Presence or absence detection

3.             Photoelectric switching or dimming (if daylight space)

Managed

(where lighting is under the control of a responsible person e.g. a hotel lounge, restaurant or shop)

1.             Time switching

2.             Presence or absence detection

3.             Photoelectric switching or   dimming (if daylight space)

Table 7: Controls for general and display lighting

The minimum required Energy Efficiency Ratios (EER) of comfort cooling equipment have been updated as detailed in table 8.

Comfort Cooling Equipment

Required Minimum Energy Efficiency Ratio (EER)

Package air conditioners - single duct types

2.5

Packaged air conditioners - other types

2.5

Split and multi-split air conditioners including variable refrigerant flow systems

2.5

Vapour compression cycle chillers - water cooled <750kW

3.85

Vapour compression cycle chillers - water cooled >750kW

4.65

Vapour compression cycle chillers - air cooled <750kW

2.5

Vapour compression cycle chillers - air cooled >750kW

2.6

Water loop heat pump

3.2

Absorption chillers

0.7

Gas fired variable refrigerant flow (VRF)

1.0

Table 8: Minimum Energy Efficiency Ratios (EER) for cooling equipment

There are significant changes to the maximum specific fan powers allowed for air distribution systems and the introduction of limits on the maximum external system pressure drop (Pa).  These are shown in table 9.  The standards proposed for existing buildings are shown in brackets.

Air Distribution System

Maximum Permissable Specific Fan Power (Watts/(Litres/s))

Maximum External System Pressure Drop (Pa)

Central mechanical ventilation including heating, cooling and heat recovery

1.8

400 supply

250 extract

Central mechanical ventilation including heating and cooling

1.8 (2.2)

400 supply

250 extract

Central mechanical ventilation including heating only

1.6 (1.6)

400 supply

250 extract

All other central mechanical ventilation systems

1.4 (1.8)

400 supply

250 extract

Zonal supply system where the fan is remote from the zone, such as a ceiling void or roof mounted units

1.2 (1.5)

200

Zonal extract system where the fan is remote from the zone

0.6 (0.6)

200

Zonal supply and extract ventilation units such as ceiling void or roof units serving a single room or zone with heating and heat recovery

2.0 (2.0)

150

Local supply and extract ventilation system such as wall/roof units serving a single area with heating and heat recovery

1.8 (1.8)

150

Local supply and extract ventilation system such as wall/roof units serving a single area

0.4 (0.5)

30

Other local ventilation units

0.6 (0.6)

30

Fan assisted terminal Variable Air Volume (VAV) unit

1.2 (1.2)

30

Fan coiled units

0.6 (0.6)

30

Table 9: Air distribution systems